Max. continuous operating voltage (DC) | UCPV *(+) PE/(-) PE | 75V | 300V | 600V | 1000V |
Nominal discharge current (8/20) | In (+) PE/(-) PE | 10kA | 20kA | 20kA | 12.5kA |
Max. discharge current (8/20) | Imax (+) PE/(-) PE | 20kA | 40kA | 40kA | 25kA |
Short-circuit withstand | ISCPV | 1000A | 1000A | 1000A | 1000A |
Protection level | Up (+) PE/(-) PE | < 0.8kV | < 1.5kV | < 2.3kV | < 2.8kV |
Residual voltage at 5kA (8/20) | Ures | < 0.6kV | < 1.1kV | < 1.6kV | < 2.2kV |
Follow current | Ifi | NO | NO | NO | NO |
Response time | tA | < 25ns | < 25ns | < 25ns | < 25ns |
Thermal protection | | YES | YES | YES | YES |
Ground fault withstand (DC) | | 120V | 450V | 900V | 1500V |
Mechanical characteristics | Mechanical characteristics | Mechanical characteristics | Mechanical characteristics | Mechanical characteristics | Mechanical characteristics |
Temperature range | | - 40˚C ….+ 80˚C | - 40oC ….+ 80oC | - 40oC ….+ 80oC | - 40oC ….+ 80oC |
Terminal screw torque | | max. 3.0Nm | max. 3.0Nm | max. 3.0Nm | max. 3.0Nm |
Terminal cross section | | 35mm² (solid) / 25mm² (stranded) | 35mm2 (solid) / 25mm2 (stranded) | 35mm2 (solid) / 25mm2 (stranded) | 35mm2 (solid) / 25mm2 (stranded) |
Mounting | | 35mm DIN rail, EN 60715 | 35mm DIN rail, EN 60715 | 35mm DIN rail, EN 60715 | 35mm DIN rail, EN 60715 |
Degree of protection | | IP 20 | IP 20 | IP 20 | IP 20 |
Housing material | | Thermoplastic; extinguishing degree UL 94 V-0 | Thermoplastic; extinguishing degree UL 94 V-0 | Thermoplastic; extinguishing degree UL 94 V-0 | Thermoplastic; extinguishing degree UL 94 V-0 |
Indication of disconnector operation | | red flag | red flag | red flag | red flag |
Remote contacts (RC) | | YES | YES | YES | YES |
Contact ratings | | AC: 250V/0.5A; 125V/3A | AC: 250V/0.5A; 125V/3A | AC: 250V/0.5A; 125V/3A | AC: 250V/0.5A; 125V/3A |
Terminal cross section | | max. 1.5mm² | max. 1.5mm2 | max. 1.5mm2 | max. 1.5mm2 |
Remote terminal torque | | 0.25Nm | 0.25Nm | 0.25Nm | 0.25Nm |