Attribute | Unit | PM3 (2-8kV) SSW |
Maximum rated voltage | kV | 8 |
Rated voltage range | kV | 2 - 8 |
THD (V) | % | 10 |
BIL | kV | 95 |
Rated frequency | Hz | 50/60 |
Ambient temperature - minimum | °C | -40 |
Ambient temperature - maximum | °C | +55 |
Altitude | masl | Up to 2000 |
| | |
Specification | | |
Attribute | Unit | PM3 (2-8kV) SSW |
Rated capacitance | μF | 3 x 0,2 |
Capacitance tolerance | % | -5/+5 |
Resistance per phase | Ω | 30 |
Tangent Delta | | 20 x 10-4 |
Dielectric type | | all-film |
Bushings: Impulse test voltage Dry test voltage Wet test voltage Minimum creepage | kV kV kV mm | 953828305 |
Installation location | | Machine Mount (MM) |
Fusing | | No internal fusing |
| | |
Routine tests | | |
Voltage withstand terminal -terminal | kV dc | 18,06kV DC for 10s |
Voltage test terminal-ground | kV ac | 9,03kV AC for 10s |
Tangent delta | | Yes |
Capacitance | | Yes |
| | |
Reliability | | |
Maintenance requirements | | None |
Performance verification | | Via the safety switch |
Expected service life | | >15 years |
| | |
Construction | | |
Phases | | Three phase |
Enclosure fabrication | | Welded |
Enclosure material | | 304 Stainless steel |
Primer | | Epoxy |
Finish | | PUR RAL 7032 |
Connection | | YN |
Bushing quantity | | 3 |
Bushing type | | Ceramic |
Insulation | | Fluid |
Fluid type | | Jarylec C101D |
Fluid volume | litre | 6 |
Weight | kg | 22 |
Overall Dimensions (L x H x W) | mm | 520x520x105 |
| | |
Standards | | |
Explosion Protected Ex nA llC T3A | | Yes |
Routine tests | | IEC 60871-1: 2005 |
Temperature category | °C | -25/D (-25/+80) |
Quality Management System | | ISO 9001:2008 ISO 14001:2004 |
Certification Body | | Bureau VERITAS |
In compliance with | | IEC 60871-1: 2014; VDE 0560 Teil 410; ANSI/IEEE 18-2002; NEMA CP-1-2000 |
Marks | | CE IA |
| | |
Options | | |
Safety switch | | Yes |
Partial discharge sensor | | No |
| | |
Shipping | | |
Anti-static link | | Yes |